Pepperl+Fuchs SMART Transmitter Power Supply KCD2-STC-EX1

Category:
Pepperl+Fuchs SMART Transmitter Power Supply KCD2-STC-EX1

 

Key Benefits at a Glance

  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for 2-wire SMART transmitters and current sources
  • Output for 4 mA … 20 mA or 1 V … 5 V
  • Housing width 12.5 mm
  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508
Pepperl+Fuchs SMART Transmitter Power Supply KCD2-STC-EX1

 

This isolated barrier is used for intrinsic safety applications.

The device supplies 2-wire SMART transmitters in a hazardous area, and can also be used with 2-wire SMART current sources.

It transfers the analog input signal to the safe area as an isolated current value.

Digital signals may be superimposed on the input signal in the hazardous or safe area and are transferred bi-directionally.

Selectable output of current source, sink mode, or voltage output is available via DIP switches.

If the HART communication resistance in the loop is too low, the internal resistance of 250 Ω between terminals 6 and 8 can be used.

Test sockets for the connection of HART communicators are integrated into the terminals of the device.

 

Pepperl+Fuchs SMART Transmitter Power Supply KCD2-STC-EX1

 

Connection Power Rail or terminals 9+, 10-
Rated voltage Ur 19 … 30 V DC
Ripple ≤ 10 %
Rated current Ir ≤ 45 mA at 24 V and 20 mA source mode output
Power dissipation ≤ 800 mW
Power consumption ≤ 1.1 W